Kamstrup MULTICAL 603 Datasheet.pdf
Data sheet
MULTICAL® 603
The future-proof heat and
cooling meter with full flexibility
• Fully programmable data logger with minute
loggers
• 2-second integration interval
• 16-years battery lifetime at a reading interval
down to 10 seconds
• Possibility of built-in M-Bus
• 2 communication modules
• 7- or 8-digit display resolution
• User-friendly interface with 3 push buttons
• Possibility of backlit display
• Auto Detect of ULTRAFLOW®
• Mixed fluid compatible
MID 2014/32/EU
M24 0200
EN 1434
DK-BEK 1178 – 06/11/2014
16 9
EN 1434
MULTICAL® 603
Contents
Description 3
Mechanical design 4
Mechanical data 4
Approved meter data 5
Accuracy 6
Dimensioned sketches 7
Electrical data 8
Product variants 10
Meter configuration 12
Information codes in display 14
Accessories 15
2 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Description
MULTICAL® 603 is an all-round calculator, suitable as heat been specially designed with a view to obtaining long lifetime
meter, cooling meter or combined heat/cooling meter and sharp contrast in a wide temperature range. Further-
together with 1 or 2 flow sensors and 2 or 3 temperature more, MULTICAL® 603 can be delivered in a variant with
sensors. The meter is intended for energy measurement in backlit display (type 603-F).
almost all types of thermal installations where water is used MULTICAL® 603 is powered by an internal D-cell lithium bat-
as the energy-conveying medium. tery with a lifespan of up to 16 years or a 2xAA lithium packet
MULTICAL® 603 can, in addition to heat and cooling measure- with a lifespan of up to 9 years. Alternatively, the meter can
ment, be used for leakage monitoring, permanent perfor- be mains supplied, either by 24 VAC or 230 VAC.
mance monitoring, as power and flow limiter with valve In designing MULTICAL® 603, great importance has been
control as well as for energy measurement in both open and attached to flexibility through programmable functions and
closed systems. plug-in modules in order to secure optimum use in a wide
According to EN 1434 and MID, MULTICAL® 603 can be desig- range of applications. The meter has been configured from
nated as a ”calculator” with separate type approval and verifi- the factory and is ready for use. It can, however, be changed/
cation, and it can be delivered either as a separate calculator reconfigured after installation via the front keys of the meter,
or as a complete meter, with mounted temperature sensors READy or METERTOOL HCW.
and flow sensor according to customer requirements. Auto Detect enables the exchange of ULTRAFLOW® X4 on
MULTICAL® 603 has 2 flow sensor inputs that can be used MULTICAL® 603 without the need for reconfiguration (change
for both electronic and mechanical flow sensors. The pulse of the CCC code). MULTICAL® 603 can automatically adjust
figure can be programmed from 0.001 to 300 pulses/liter, the pulse figure and qp to match the connected ULTRAFLOW®
and the calculator can be programmed to all nominal flow X4 via Auto Detect. Auto Detect is active with CCC code 8xx
sensor sizes from 0.6 to 15,000 m³/h. The calculator can be and is initiated when the calculator top and base are sepa-
delivered with both galvanically connected and separated rated and reassembled.
flow sensor inputs.
The accumulated heat energy and/or cooling energy can be
displayed in kWh, MWh, GJ or Gcal, all in the form of seven or
eight significant digits plus measuring unit. The display has
Kamstrup A/S • FILE100000683_G_EN_08.2024 3
MULTICAL® 603
Mechanical design
5
7 8
3
6 4 2 1
1 Calculator top with front keys and laser engraving 5 … or a battery can be mounted
2 PCB with microcontroller, display, etc. 6 1 or 2 communication modules
3 Verification cover (may only be opened at an authorised laboratory) 7 Connection of temperature sensors and flow
4 Either a power supply module can be mounted… sensors
8 Calculator base
Mechanical data
Weight 450 g
Ambient temperature 5…55 °C. Non-condensing, closed location (indoor installation)
Protection class IP65
Medium temperatures ULTRAFLOW® 2…130 °C At medium temperatures below ambient temperature or
above 90 °C in the flow sensor, we recommend that the
calculator is wall-mounted.
Medium in ULTRAFLOW® Water (district heating water as described in AGFW FW510)
Storage temperature -25…60 °C (drained flow sensor)
Connection cable ø3.5…6 mm
Supply cable ø5…8 mm
Materials
Calculator case
– Top and base Thermoplastic, PC 10 % GF with TPE (thermoplastic elastomer)
– Verification cover ABS
Cables Silicone cable with inner Teflon insulation
4 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Approved meter data
Approvals
– Heat meter DK-0200-MI004-040
- Temperature range θ: 2 °C…180 °C The stated minimum temperatures apply to
the type approval only. The meter has no cut-
- Differential area ∆Θ: 3 K…178 K
off for low temperature and thus measures
– Cooling meter TS 27.02 012 as low temperatures as 0.01 °C and 0.01 K.
- Temperature range θ: 2 °C…180 °C
- Differential area ∆Θ: 3 K…178 K
– Bifunctional heat/cooling meter Marked with DK-0200-MI004-040 and TS 27.02 012 as well as yearly mark of MID
- Temperature range θ: 2 °C…180 °C
- Differential area ΔΘ: 3 K…178 K
– Mixed fluid meter EN 1434 without MID approval The temperature area -40 °C ...140 °C indicates the
- Temperature range θ: -40 °C…140 °C technical functional area in which the calculator
- Differential area ΔΘ: 3 K…180 K calculates energy.
The temperature area for any installation depends
on the design of the installation and the type of
fluid and solution used.
Standard EN 1434:2007/AC:2007
EN 1434:2015+A1:2018
EN 1434:2022
EU directives Measuring Instrument Directive
Low Voltage Directive
Electromagnetic Compatibility Directive
Radio Equipment Directive
RoHS Directive
Pressurised Equipment Directive
EN 1434 designation Environmental class A and C
MID designation
– Mechanical environment Class M1 and M2
– Electromagnetic environment Class E1 and E2 Non-condensing environment, closed location (indoors), 5…55°C
Temperature sensor connection
– Type 603-A Pt100 – EN 60751, 2-wire connection
– Type 603-B Pt100 – EN 60751, 4-wire connection
– Type 603-C/E/F/M Pt500 – EN 60751, 2-wire connection
– Type 603-D/G/H Pt500 – EN 60751, 4-wire connection
Kamstrup A/S • FILE100000683_G_EN_08.2024 5
MULTICAL® 603
Accuracy
Heat meter components MPE according to EN 1434-1 Typical accuracy
MULTICAL® 603 Ec = ± (0.5 + ∆Θ min/∆Θ) % Ec = ± (0.15 + 2/∆Θ) %
ULTRAFLOW® Ef = ± (2 + 0.02 qp/q), but not above ± 5 % Ef = ± (1 + 0.01 qp/q) %
Temperature sensor set Et = ± (0.5 + 3 ∆Θ min/∆Θ) % Et = ± (0.4 + 4/∆Θ) %
MULTICAL® 603 and ULTRAFLOW® qp 1.5 m³/h @∆Θ 30K
Total typical accuracy of MULTICAL® 603, sensor pair and ULTRAFLOW® compared to EN 1434-1.
MULTICAL® 403 qp 1,5 m³/h @∆Θ 30K
Ec+Et+Ef (EN) Ec+Et+Ef (Typ)
MULTICAL® 403 qp 1,5 m³/h @∆Θ 30K
Ec+Et+Ef (EN) Ec+Et+Ef (Typ)
6,0
4,0
2,0
Tol [%]
0,0
0,01 0,10 1,00 10,00
0,10 1,00 10,00
-2,0
-4,0
-6,0
q [m³/h]
q [m³/h]
6 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Dimensioned sketches
All measurements in [mm].
Mechanical measurements for MULTICAL® 603 calculator 0 0 1 Bracket for wall mounting
1 2 2 3 3 4 4 5
A A
154 154 47 47
4,
5
4,
5
,2
,2
30
30
R2
R2
11 32
11 32 13 13
11
7
11
7
B B
154 47
40
40
32
32
102
102
74
74
C C
102
166 166 11 37
11 37
58 58
D D
75
166
Wall
Title: Bracket - 3026-207
Wall Bracket - 3026-2
Calculator base separate and mounted on ULTRAFLOW®
Tolerances, unless otherwise stated:
Tolerances, unless otherwise stated:Title:
- -
Data: - Data: -
Material, ROHS Compliant: Const.:
Material, ROHS Compliant: - First issue:
Const.: - 2018-09-24 Date: 2018-09-24
First issue: 2018-09-24 Date: 2
- - Scale: Doc. No.: Doc. No.:
Scale: Rev.: Page / of
QA: - 1:1 QA: - S1334_4
1:1 S1334_4
A1 1 1
E E
75
MULTICAL® 603 mounted on ULTRAFLOW® with G¾ threaded connection
75
75
78
Kamstrup A/S • FILE100000683_G_EN_08.2024 7
MULTICAL® 603
Electrical data
Calculator data
Display LCD – 7 or 8 digits, digit height 8.2 mm
Resolutions 999,9999 - 9999,999 – 99999,99 – 999999,9 – 9999999
9999,9999 - 99999,999 – 999999,99 – 9999999,9 – 99999999
Energy units MWh – kWh – GJ – Gcal
Data logger (EEPROM)
– Logger contents Programmable – all registers can be selected
– Logging interval Programmable – from 1 minute to 1 year
– Logging depth Programmable – standard: 20 years, 36 months, 460 days, 72 hours
Info logger (EEPROM) 250 info codes (last 50 are shown in the display)
Clock/calender (with backup battery) Clock, calendar, leap year compensation, target date
Daylight saving time/wintertime (DST) Programmable
This function can be disabled so that ”technical normal time” is used
Time accuracy Without external adjustment: Less than 15 min./year
With external adjustment every 48 hours: Less than 7 s from legal time
Data communication KMP protocol with CRC16 used for optical communication as well as for modules
Power in temperature sensors < 10 µW RMS
Power supply 3.6 VDC ± 0.1 VDC
8 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Electrical data
Battery
3.65 VDC, 3.65 VDC,
D-cell lithium 2xA cell lithium
Wall-mounted 16 years @ tBAT < 30 °C 9 years @ tBAT < 30 °C
Mounted on flow sensor 14 years @ tBAT < 40 °C 7 years @ tBAT < 40 °C
Note: Depends on the meter and module configuration
Battery lifetime expected for a meter Up to 16 years (daily transmission) depending on the installation site and the NB-
fitted with a NB-IoT module IoT coverage level called ”CE level”
CElevel
CE level00
CE level C-Cell IoT
0 Up to 16 years CElevel
CE level11
1 Up to 15 years
CElevel
CE level22
2 Up to 12 years
Mains supply 230 VAC +15/-30 %, 50/60 Hz
24 VAC ±50 %, 50/60 Hz or 24 VDC +75/-25 % (24 VDC only High Power SMPS)
Insulation voltage 3.75 kV
Power consumption <1W
Backup supply Integrated supercap eliminates interruptions due to short-term power failures
(only supply modules type 7 and 8)
Kamstrup A/S • FILE100000683_G_EN_08.2024 9
MULTICAL® 603
Electrical data
Temperature measurement t1 t2 t3 t4 ∆Θ (t1-t2) ∆Θ (t2-t1) t5
Inlet Outlet Control Extra Heat Cooling Preset for A1 and A2
measurement measurement
Measuring range
603-A, 2-wire, Pt100 0.00…185.00 °C (t1 and t2: Approved for 2.00…180.00°C)
603-B, 4-wire, Pt100 0.00…185.00 °C (t1 and t2: Approved for 2.00…180.00°C)
603-C/E/F, 2-wire, Pt500 0.00…185.00 °C (t1 and t2: Approved for 2.00…180.00°C)
603-D/G/H, 4-wire, Pt500 0.00…185.00 °C (t1 and t2: Approved for 2.00…180.00°C)
603-M, 2-wire, Pt500 -42,00…143,00 °C (Labelled -40 °C…140 °C on the meter)
Offset adjustment ± 0.99 K joint zero point adjustment for t1, t2 and t3
Note: The offset adjustment is only active on measured temperatures. If, for example, t3 has been
selected for a preset value, the offset adjustment will not influence the preset value.
Max cable lengths Pt100, 2-wire Pt100, 4-wire Pt500, 2-wire Pt500, 4-wire
(max ø6 mm cable)
2 x 0.25 mm²: 2.5 m 4 x 0.25 mm²: 100 m 2 x 0.25 mm²: 10 m 4 x 0.25 mm²: 100 m
2 x 0.50 mm²: 5 m
2 x 1.00 mm²: 10 m
Flow measurement V1/V2 ULTRAFLOW® Reed contacts FET contacts 24 V active pulses
V1: 9-10-11 V1: 10-11 V1: 10-11 V1: 10B-11B
V2: 9-69-11 V2: 69-11 V2: 69-11 V2: 69B-79B
CCC-code 1xx-2xx-4xx-5xx-8xx 0xx 9xx 2xx and 9xx
EN 1434 pulse class IC IB IB (IA)
Pulse input 680 kΩ pull-up to 3.6 V 680 kΩ pull-up to 3.6 V 680 kΩ pull-up to 3.6 V 12 mA at 24 V
Pulse ON < 0.4 V in > 1 ms < 0.4 V in > 300 ms < 0.4 V in > 30 ms < 4 V in > 3 ms
Pulse OFF > 2.5 V in > 4 ms > 2.5 V in > 100 ms > 2.5 V in > 70 ms > 12 V in > 4 ms
Pulse frequency < 128 Hz < 1 Hz < 8 Hz < 128 Hz
Integration frequency < 1 Hz < 1 Hz < 1 Hz < 1 Hz
Electrical isolation No No No 2 kV
Max cable length 10 m 10 m 10 m 100 m
Max cable length with 30 m 30 m 30 m -
Cable Extender Box, Type 66-99-036
Pulse inputs In-A/In-B Electronic switch Reed-switch
Pulse input 680 kΩ pull-up to 3.6 V 680 kΩ pull-up to 3.6 V
Pulse ON < 0.4 V in > 30 ms < 0.4 V in > 500 ms
Pulse OFF > 2.5 V in > 30 ms > 2.5 V in > 500 ms
Pulse frequency < 3 Hz < 1 Hz
Electrical isolation No No
Max cable length 25 m 25 m
Requirements to external contact Leakage current at function open < 1 µA
Pulse outputs Out-C/Out-D HC-003-11 (before 2017-05) HC-003-11 (after 2017-05)
HC-003-21/-31 (before 2018-04) HC-003-21/-31 (after 2018-04)
Pulse output type Open collector (OB) Opto FET
External voltage 5…30 VDC 1…48 VDC/VAC
Current < 10 mA < 50 mA
Residual stress UCE ≈ 1 V at 10 mA RON ≤ 40 Ω
Electrical isolation 2 kV 2 kV
Max cable length 25 m 25 m
10 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Product variants
MULTICAL® 603 type number Static data Dynamic data
Written on the Appearing from display
meter’s front
603-X X XX – X XX X XX XX
Type 603- –
Calculator type
Pt100 2-wire t1-t2 V1 M-Bus A
Pt100 4-wire t1-t2 V1 M-Bus B
Pt500 2-wire t1-t2 V1 M-Bus C
Pt500 4-wire t1-t2 V1 M-Bus D
Pt500 2-wire t1-t2-t3 V1-V2 E
Pt500 2-wire t1-t2-t3 V1-V2 Backlit display F
Pt500 4-wire t1-t2 V1 (24 V active pulses) M-Bus G
Pt500 4-wire t1-t2-t3 V1-V2 H
Pt500 2-wire t1-t2-t3 V1-V2 (Mixed fluid only) M
Meter type
Heat meter MID module B 1
Heat meter MID module B+D 2
Heat/cooling meter MID module B+D & TS 27.02 * θHC = OFF 3
Heat meter National approval 4
Cooling meter TS 27.02+BEK1178 5
Heat/cooling meter MID module B+D & TS 27.02 * θHC = ON 6
Volume meter, hot 7
Volume meter, cold 8
Energy meter 9
Country code
Determined by Kamstrup upon receipt of order XX
* In some countries bi-functional meters type 3 and 6 are only allowed to be assigned with the MID marking, due to national law.
Kamstrup A/S • FILE100000683_G_EN_08.2024 11
MULTICAL® 603
Product variants
MULTICAL® 603 type number Static data Dynamic data
Written on the Appearing from display
meter’s front
603-X XX X – X XX X XX XX
Type 603- –
Flow sensor connection type
Delivered with one ULTRAFLOW® 1
Delivered with two identical ULTRAFLOW® 2
Prepared for one ULTRAFLOW® 7
Prepared for two identical ULTRAFLOW® 8
Prepared for flow sensor with fast and bounce-free electronic pulses C
Prepared for flow sensor with slow and bounce-free electronic pulses J
Prepared for flow sensor with slow pulses with bounce L
Prepared for flow sensor with 24 V active pulses P
Delivered with one flow sensor (Mixed fluid only) G
Temperature sensor set
Supplied without temperature sensors 00
2-wire Pt500 temperature sensors
Direct short temperature sensors, 2 pcs. DS 27.5 mm L 1.5 m - 3.0 m 5x
Direct short temperature sensors, 2 pcs. DS 38.0 mm L 1.5 m - 3.0 m 2x
Pocket temperature sensors, 2 pcs. PL ø5.8 mm 1.5 m - 10 m 8x
2-wire Pt100 temperature sensors
Direct short temperature sensors, 2 pcs. DS 27.5 mm L 2.0 m J6
4-wire Pt500/Pt100 temperature sensors
Pocket temperature sensors with connection head, 2 pcs. PL ø6.0 mm L 105 mm - 230 mm Ax
Pocket temperature sensors with connection head, 2 pcs. PL ø5.8 mm L 65 mm - 180 mm Cx
Supply
No supply 0
Battery, 1 x D-cell 2
230 VAC high-power SMPS 3
24 VAC/VDC high-power SMPS 4
Battery, 1 x D-cell IoT 5
230 VAC power supply 7
24 VAC power supply 8
Battery, 2 x A-cells 9
Communication module (2 module slots) M1 M2
No module 00 00
Data Pulse, inputs (In-A, In-B) 10 10
Data Pulse, outputs (Out-C, Out-D) 11 11
Wired M-Bus, inputs (In-A, In-B) 20 20
Wired M-Bus, outputs (Out-C, Out-D) 21 21
Wired M-Bus, Thermal Disconnect 22 22
linkIQ/wM-Bus, inputs (In-A, In-B), EU 32 32
linkIQ/wM-Bus, outputs (Out-C, Out-D), EU 33 33
wM-Bus, inputs (In-A, In-B), 912,5/915/918,5 MHz 34 34
Analog outputs 2 x 0/4…20 mA 40 40
Analog inputs 2 x 4…20 mA/0…10 V 41 41
PQT Controller 43 43
Low Power Radio, inputs (In-A, In-B), 434 MHz 50 50
Low Power Radio GDPR, inputs (In-A, In-B), 434 MHz 51 51
NB-IoT, inputs (In-A, In-B) 56
LON TP/FT-10, inputs (In-A, In-B) 60 60
BACnet MS/TP, inputs (In-A, In-B) 66 66
Modbus RTU, inputs (In-A, In-B) 67 67
2G/4G Network 80 80
BACnet IP, inputs (In-A, In-B) 81 81
Modbus/KMP TCP/IP, inputs (In-A, In-B) 82 82
READy TCP/IP, inputs (In-A,In-B) 83 83
High Power Radio Router, inputs (In-A, In-B), 444 MHz 84 84
High Power Radio Router GDPR, inputs (In-A, In-B), 444 MHz 85 85
Contact Kamstrup A/S for further information about product variants.
12 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Meter configuration
A - B - CCC - DDD - EE - FF - GG - L - M - N -
-
PP - RR - T - VVVV
Flow sensor position
Inlet 3
Outlet 4
Measuring unit
GJ 2
kWh 3
MWh 4
Gcal 5
Auto Detect CCC codes (UF x4)
Normal resolution (7 digits) 807
High resolution (8 digits) 818
Static CCC codes
Reed contact (7 digits) 0xx
Electronic, fast pulses (7 digits) 1xx
Electronic, fast pulses (8 digits) 2xx
Kamstrup, UF X4 (7 digits) 4xx
Kamstrup, UF X4 (8 digits) 5xx
Electronic, slow pulses (7 digits) 9xx
Display
Heat meter (standard) 210
Heat/cooling meter (standard) 310
Cooling meter (standard) 510
Tariffs
No active tariff 00
Power tariff 11
Flow tariff 12
t1-t2 tariff 13
Inlet tariff 14
Outlet tariff 15
Time-controlled tariff 19
Heat/cooling volume tariff 20
PQ tariff 21
Pulse inputs In-A/In-B
10 m³/h, 10 l/imp, pre-counter 1 (standard) 24 24
Integration mode
Adaptive mode (2-64 s) Display on 1
Normal mode (32 s) Display on 2
Fast mode (8 s) Display on 3
Fast mode (2 s) Display on 4
Adaptive mode (2-64 s) Display off 5
Normal mode (32 s) Display off 6
Fast mode (8 s) Display off 7
Leakage limits (V1/V2)
OFF 0
1.0 % of qp + 20 % of q 1
1.0 % of qp + 10 % of q 2
0.5 % of qp + 20 % of q 3
0.5 % of qp + 10 % of q 4
Cold water leakage limits (In-A/In-B)
OFF 0
30 min. without pulses 1
One hour without pulses 2
Two hours without pulses 3
Kamstrup A/S • FILE100000683_G_EN_08.2024 13
MULTICAL® 603
Meter configuration
A - B - CCC - DDD - EE - FF - GG - L - M - N
-
- PP - RR - T - VVVV
Pulse outputs Out-C/Out-D
Out-C: V1/4 5 ms 73
Out-C: V1/1, Out-D: V2/1 3.9 ms 80
Out-C: V1/1 3.9 ms 82
Out-C: V1/4 22 ms 83
E1 and V1 or E3 and V1 10 ms 94
E1 and V1 or E3 and V1 32 ms 95
E1 and V1 or E3 and V1 100 ms (0.1 s) 96
Controlled output based on data commands 99
Data logger profile
Standard data logger profile 30
Encryption level
Individual key 3
Customer label
Serial number 0000
Contact Kamstrup A/S for further information about meter configuration.
14 Kamstrup A/S • FILE100000683_G_EN_08.2024
MULTICAL® 603
Information codes in display
Display digit Description
1 2 3 4 5 6 7 8
Info t1 t2 t3 V1 V2 In-A In-B
1 No voltage supply
2 Low battery level
9 External alarm (e.g. via KMP)
1 t1 Above measuring range or switched off
1 t2 Above measuring range or switched off
1 t3 Above measuring range or switched off
2 t1 Below measuring range or short-circuited
2 t2 Below measuring range or short-circuited
2 t3 Below measuring range or short-circuited
9 9 t1-t2 Invalid temperature difference
1 V1 Communication error
1 V2 Communication error
2 V1 Wrong pulse figure
2 V2 Wrong pulse figure
3 V1 Air
3 V2 Air
4 V1 Wrong flow direction
4 V2 Wrong flow direction
6 V1 Increased flow (flow1 > qs, for more than 1 hour)
6 V2 Increased flow (flow2 > qs, for more than 1 hour)
7 V1/V2 Burst, water loss (flow1 > flow2)
7 V1/V2 Burst, water penetration (flow1 < flow2)
8 V1/V2 Leakage, water loss (M1 > M2)
8 V1/V2 Leakage, water penetration (M1 < M2)
7 In-A2 Leakage in the system
8 In-A1 Leakage in the system
9 In-A1/A2 External alarm
7 In-B2 Leakage in the system
8 In-B1 Leakage in the system
9 In-B1/B2 External alarm
Example:
1 0 2 0 0 0 9 0
Note: Info codes are configurable. Therefore, it is not certain that all the parameters are available in a given MULTICAL® 603.
An info logger saves the info code every time the info log is changed. It is possible to read the latest 250 changes of the info
code and the date of the change.
Kamstrup A/S • FILE100000683_G_EN_08.2024 15
MULTICAL® 603
Accessories
Article number Description
HC-993-02 Battery module with one D-cell
HC-993-03 230 VAC High Power supply module
HC-993-04 24 VAC/VDC High Power supply module
HC-993-05 Battery module with one D-cell IoT
HC-993-07 230 VAC supply module
HC-993-08 24 VAC supply module
HC-993-09 Battery module with two A-cells
2105-002 Sealing cap, G¾B (R½)
3026-1148 Sealing cap, self locking, G¾B (R½)
3026-207.A Wall bracket with screws and plugs for MULTICAL® 603
3026-517 Sealing cap for temperature sensors, blue 2 pcs.
3026-518 Sealing cap for temperature sensors, red 2 pcs.
3026-858 Angle fitting ULTRAFLOW® (qp 0.6...2.5)
3026-909 Holder for optical readout head
3026-963 Disassemble tool for MULTICAL® 603
Kamstrup A/S • FILE100000683_G_EN_08.2024
3130-262 Blind plug with O-ring
3130-269 Cable clamp with screws
5000-337 Module cable, 2 m (2 x 0.25 mm²)
6699-035 USB module configuration cable
6699-036 Cable Extender Box
6699-042 Metal plate for optical read-out head (20 pcs)
6699-047 Supply label MULTICAL® 403/603, 10 pcs. (2006-681)
6699-099 Infrared optical read-out head w/USB plug
6699-110 Panel bracket
6699-403 230/24 VAC safety transformer 5 VA
6699-404 230/24 VAC safety transformer 10 VA
6699-405 230/12/24 VAC safety transformer 63 VA
6699-447.E Internal antenna for Kamstrup radio, 434 MHz
6699-448 Mini Triangle antenna for Wireless M-Bus and 2G/4G Network Module
6699-482.E Internal antenna for Wireless M-Bus 868 MHz
6699-724 METERTOOL HCW
6699-725 LogView HCW
Calibration units
Article number Description
6699-363 2-wire Pt500, heat/cooling (used with METERTOOL HCW)
6699-364 4-wire Pt500, heat/cooling (used with METERTOOL HCW)
6699-365 2/4-wire Pt100, heat/Cooling (used with METERTOOL HCW)
For further information on MULTICAL® 603 and its accessories, please refer to the technical description, which you can find on
Kamstrup Product Centre.
Kamstrup A/S
Industrivej 28, Stilling
DK-8660 Skanderborg
T: +45 89 93 10 00
info@kamstrup.com
kamstrup.com
16 Kamstrup A/S • FILE100000683_G_EN_08.2024