Application description
CMe2100 LTE is an MBus metering gateway for mobile networks. It reads up to 256 meters, turns the readings into customised reports and sends them to the system that needs them. Through its infrared interface it also talks to Elvaco CMe and CMeX devices and to ABB electricity meters. It works with any meter that uses the MBus standard, and it is configured and updated by SMS or HTTP.
Setup over the mobile network
Installation and configuration can be done remotely. Once the unit is powered and wired, a text message from a mobile phone is enough to configure it. A single command makes the gateway search the two wire MBus line and register every meter it finds. After that it is ready to take scheduled readings and deliver push reports to any recipient, using any chosen protocol.
Setup with the mobile network
Metering and reporting
Once meters are registered, readings are taken on a schedule you set. The data is compiled into a report and delivered to a receiving system. Where little integration is needed, a simple scheduled email is enough. The gateway can also send reports by SMS, upload them to an HTTP server, or place files on an FTP server.
A built in MBus decoder returns values in a readable form, with the correct precision and unit. A local database keeps every meter value inside the unit, which makes the system robust. Push reports retry automatically, and a retry includes every value from earlier failed transmissions.
Metering with integrated statistics
Key features
- Integrated MBus master driving 16 unit loads, extendable to 256 with an Elvaco MBus master
- Customised meter value reports by HTTP, FTP and email
- Remote configuration over the mobile network
- Quick to add to an existing MBus system, whatever the meter manufacturer
Compatibility and extensions
Meter compatibility
- All types of MBus meter, regardless of manufacturer
- Elvaco temperature and humidity sensors: CMa10, CMa10w, CMa11, CMa11w, CMa12w, CMa20 and CMa20w
- ABB electricity meters fitted with an IR interface
Unit load extension
Any Elvaco MBus master can be added to increase the number of meters the gateway drives. CMe2100 LTE drives 16 unit loads by default, where one unit load is 1.5 mA, and the software limit is 256 meters depending on the licence.
Wired and Wireless MBus
The gateway can read wired MBus meters, Wireless MBus meters, or both. To read wireless meters it needs a Wireless MBus receiver, for example the Elvaco CMeX50.
Note: Elvaco extension devices (Wireless MBus receivers and MBus masters) have an IR interface, so they connect with no cabling.
Note: Elvaco can supply preconfigured turnkey box solutions from the factory.
Parts overview
Buttons and indicators
- Serial number
- Push button
- MBus connector
- Antenna SMA connector
- IR interface
- Status LED (green)
- Error LED (red)
- Network LED (yellow)
- Blue LED (not used)
- SIM card holder
- USB slave connector
- USB master connector
- Power supply L
- Power supply N
LED indications
Green and red LEDs
| Green LED | Red LED | Product state | Visual |
|---|---|---|---|
| Permanently off | Permanently off | Power off or restarting. |
|
| Permanently on | Permanently on | Power on. |
|
| 1500 ms on, 100 ms off | Permanently off | Normal operation. |
|
| 1500 ms on, 100 ms off | Permanently on | Short circuit or overcurrent on the MBus. |
|
| 1500 ms on, 100 ms off | 800 ms on, 800 ms off | No SIM card installed. |
|
| 800 ms on, 800 ms off | 800 ms on, 800 ms off | Software being updated. |
|
| 1500 ms on, 100 ms off | 100 ms on, 1500 ms off | Not connected to a network. |
|
Yellow LED
| Yellow LED | Product state | Visual |
|---|---|---|
| Permanently off | Power off or restarting. | |
| 500 ms on, 500 ms off | Limited network service: no SIM card, PIN code error, or network search in progress. | |
| 10 ms on, 1990 ms off | Data transfer in progress. | |
| 10 ms on, 3990 ms off | Registered on a network, no data transfer in progress. |
Configuration and administration
The gateway has a built in command parser for commands sent by SMS or Telnet. It replies OK when a command succeeds, or ERROR with a description when it does not. Each command has a security level, and a security code may be needed to run certain commands. Security is off by default and has to be enabled.
Configuration by SMS
The usual method is a text message sent from a mobile phone to the number of the SIM card in the unit. When security is enabled, the message must start with the security code, followed by a semicolon or line break, then the command. For example: 2222;qset email. Replies begin with the product name and serial number by default.
Example of a command sent by SMS and the reply from the unit
Configuration by Telnet
Any Telnet client can be used. When security is enabled, log in with the login command before running any other command.