DIN rail mounting
The unit clips onto a DIN rail. Use the clip on the underside to fit it to the rail or release it. For safety, a DIN rail enclosure must cover all terminals.
Installing the SIM card
The unit needs a SIM card to use the mobile network.
- Use a standard size SIM card. If it is a prepaid SIM, check it has enough credit to answer SMS commands.
- Gently press the SIM card into the holder with the chip facing right.
Connecting the power supply
- Connect the mains supply to the screw terminals marked L and N. The supply must be 100 to 240 VAC, 50/60 Hz.
- Fit a clearly marked, easily reached switch in the supply so the unit can be isolated for maintenance or service.
MBus terminal
MBus is a two wire bus with no polarity, and several meters can share it. The terminal on CMe2100 LTE drives up to 16 meters directly. With an MBus expander from the Elvaco range this can be extended to 256 meters. Connect the meters with cable of 0.25 to 1.5 mm2 cross section, for example standard telephone cable (EKKX 2x2x0.5).
Antenna connection
CMe2100 LTE needs an external antenna on the SMA connector. Antennas are ordered separately, and the Elvaco accessories range includes options for different locations.
IR interface
The IR interface lets CMe2100 LTE talk to Elvaco MBus masters, Wireless MBus receivers (CMeX series) and ABB electricity meters without cables. Mount the unit next to the other device so the two IR windows face each other, and remove the IR shield before use.
USB connectors
The USB master and USB slave ports are reserved for future product features.
Wiring diagram
Wiring summary
| Connection | Terminal or port | Notes |
|---|---|---|
| Mains supply | L and N screw terminals | 100 to 240 VAC, 50/60 Hz, 10 A type C protection |
| MBus meters | MBus connector | Two wire, no polarity, up to 1000 m of cable |
| Antenna | SMA connector | External antenna, sold separately |
| SIM card | SIM card holder | Standard size, no PIN |
| Other Elvaco units | IR interface | Face the IR windows together, remove the IR shield |
| Computer or future use | USB slave and USB master | Reserved for upcoming features |
Quick start using default settings
Once the unit is mounted, powered and wired to its meters, two commands get it running. After them it will read every installed meter once an hour at 2400 bit/s, and send an email push report at 00:00 each day.
- Set the email recipient of the daily report: qset email [recipient]. The unit replies by SMS to confirm.
- Start the meter installation: install [expected number of meters]. The unit replies by SMS when the installation starts, and again when it finishes.
| Variable | Explanation | Setting |
|---|---|---|
| Recipient | The email address that receives the daily push report. | A valid email address |
| Expected number of meters | How many meters the unit should expect to find during installation. | Any whole number |